Article - CS333207
Can the TSXCUSBMBP USB Modbus Plus Communications Adapter be Used with KEPServerEX?
Modified: 02-Nov-2020
Applies To
- Kepware Server (formerly KEPServerEX) 5.19.467.0 to 6.8
- ThingWorx Kepware Server (legacy) 8.0 to 8.4
Description
Yes, it can; however, the appropriate Modbus driver must be used depending on the TSXCUSBMBP revision. Revision 1 utilizes a virtual serial port and must be used in conjunction with Kepware's Modbus RTU Serial Driver. For more information on configuring a TSXCUSBMBP Revision 1 adapter, refer to TSXCUSBMBP USB Adapter Connectivity Guide . Revision 2 is configured like an internal Modbus Plus adapter. It is a direct bridge between Kepware's Modbus Plus Driver and the Modbus Plus network.
This is a printer-friendly version of Article 333207 and may be out of date. For the latest version click CS333207